Communication objects — Presence detector — Constant light controller
11.16
Communication objects — Presence detector — Constant light controller

11.16.1 Px: Output 1

Number
1 | 19
The respective control value is sent to the actuator via the output. When output 2 is active,
output 1 is to activated the light row with the largest distance to the window and output 2 with
the smallest distance to the window.

11.16.2 Px: Output 2

Number
2 | 20
The respective control value is sent to the actuator via the output. When output 2 is active,
output 1 is to activated the light row with the largest distance to the window and output 2 with
the smallest distance to the window.

11.16.3 Px: Automatic / manual off

Number
3 | 21
The control can be activated (automatic) or deactivated (manual) via the object. If the object is
connected to a control element, the control is deactivated with a 0 and activated with a 1. (0 =
manual off, 1 = automatic).

11.16.4 Px: Relative dimming (dimmer)

Number
4 | 22
The object can be connected to a control element. This makes it possible to dim the lights
brighter / darker in the room. The constant light controller is deactivated.

11.16.5 Px: Value (dimmer)

Number
5 | 23
The object can be connected to a value sender. This makes it possible to regulate the lighting in
the room manually. The constant light controller is deactivated.
KNX Technical Manual 2CKA001473B8667 │ 06.02.2017
Description of application and parameters
Name
Px: Output 1
Name
Px: Output 2
Name
Px: Automatic / manual off
Name
Px: Relative dimming (dimmer)
Name
Px: Value (dimmer)
Object function
Output
Object function
Output
Object function
Input
Object function
Input
Object function
Input
Data type
5.001 percentage
(0..100%)
5.010 counter pulses
(0..255)
Data type
5.001 percentage
(0..100%)
5.010 counter pulses
(0..255)
Data type
1.001 switch
Data type
3.007 dimming control
Data type
5.001 percentage
(0..100%)