11.3.25 Extended parameter settings — Pause time (ss.fff)
Options:
The set pause time is started after the detector has been switched off due to expiry of the
switch-off delay or when a switch-off telegram is received on objects "external push-button"
or "actuator status".
If movement is detected during this time, the detector is not switched on immediately. The
pause time is first extended by 7 seconds. If there is still movement after these 7 seconds,
the detector switches back on.
If no movement is detected during the pause time, the detector is ready for activation again
after the pause time.
This behaviour can, for example, be important when the lamp cools down drastically and is
located within the detection range of the detector. Without a blockage there would be an
unintentional switch-on. The purpose of pause time is to prevent an immediate re-activation.
Example: The person switches the light off manually when leaving the room. Without the
pause time the detected movement would cause a renewed switch-on during exiting.
Note
11.3.26 Extended parameter settings — Overwriting settings during a download
Options:
Yes: When the application is reloaded into the detector, the values changed via the bus are
overwritten with the parameterised values of the ETS application.
No: When the application is reloaded into the detector, the values changed via the bus are
not overwritten with the parameterised values of the ETS application.
Values:
Switch-off delays
External/internal brightness threshold
Brightness correction (daylight), see "Brightness detection" application
KNX Technical Manual 2CKA001473B8667 │ 06.02.2017
Description of application and parameters
00.100 .. 01,250 .. 59,999
The "external push-button" object is activated under the "External push-
button" parameter.
The "actuator status" object is activated under the "status display"
parameter.
Yes
No
"Detector" application