6.4.2
"Surface-mounted" ceiling mounting with surface -mounted housing (optional housing,
article no. 6131/x9)
KNX Technical Manual 2CKA001473B8667 │ 06.02.2017
Slide the KNX bus line into the surface-mounted
■
housing through one of the specified openings. A
sufficient length of KNX bus line must project from the
hole.
Fasten the surface-mounting housing with screws.
■
Remove the two clamps on the device with the aid of
■
a screwdriver and dispose of them.
Connection of the integrated KNX bus coupler (rear
of the device):
Connect the KNX bus line with the enclosed 2-pole
■
bus connection terminal (see connection diagram in
Chapter 5.3). The connection is reverse polarity
protected!
Slide the bus connection terminal into the push-on
■
fixture provided.
Mounting