Condensate Water Alarm; Outside Temperature For Summer Compensation; Summer Compensation Active - Busch-Jaeger mini KNX 6131/20 series Technical Manual

Presence detector knx
Table of Contents

Advertisement

11.19.31 Condensate water alarm

Number
29
This 1-bit communication object is used to place the controller in the condensation alarm mode.
This causes the current setpoint value to be set to the heat protection setpoint value in order to
keep the structure from being damaged by an overflowing condensation container.
Note
Item 1:
This protective mechanism is only active in the cooling mode. It remains in place
until it is cancelled by the value (0). When an alarm is active, manual operation
of the controller is blocked. This information is indicated by a corresponding icon
on the device.
Item 2:
This protective mechanism is only active in the cooling mode. It remains in place
until it is cancelled by the value (0). When an alarm is active, manual operation
of the controller is blocked. This information is indicated by a corresponding icon
on the device.
When the master/slave mode is active, the condensate water alarm
(master/slave) objects must be connected to the alarm transmitter.

11.19.32 Outside temperature for summer compensation

Number
30
In order to save energy, and to ensure that the temperature difference occurring during entry
and exit of a climate-controlled building stays within comfortable limits, the reduction of room
temperature by cooling devices should be limited as a function of the outside temperature
(summer compensation). This, for example, prevents the air-conditioning system from further
reducing the room temperature to 24°C with an outside temperature of 35°C.
This function can only be used with an outside temperature sensor. This 2-byte communication
object must then be used to provide the controller with the current outside temperature.

11.19.33 Summer compensation active

Number
31
This 1-bit communication object is used to indicate via the bus whether the summer
compensation is active (1) or inactive (0). If it is active, the setpoint value configured for the
cooling mode is increased by the summer compensation function. A decrease of the cooling
mode setpoint temperature below the value calculated by the parameterised summer
compensation function is not possible. An increase of the setpoint temperature for the cooling
mode is always possible.
KNX Technical Manual 2CKA001473B8667 │ 06.02.2017
Description of application and parameters
Name
1. Condensate water alarm
2. Condensate water alarm
(master/slave)
Name
Outside temperature for summer
compensation
Name
Summer compensation active
Communication objects — Object RTC
Object function
Input
Input
Object function
Input
Object function
Output
Data type
Switching
Switching
Data type
2-byte floating point
value
Data type
Switching
│190