11.4.32 Enable — Use of presence detector enable object
Options:
No: There is no object with which the constant light switch can be blocked or enabled.
Yes: A 1-bit "enable presence" communication object (input) is being enabled. This object
allows the constant light switch to be enabled or blocked. No telegrams are sent by the
detector during blockage.
11.4.33 Enable — Enable with
Options:
On telegram: With the receipt of value 1 on the enable movement (input) object, the detector
is enabled and blocked with value 0.
Off telegram: With the receipt of value 0 on the enable movement (input) object, the detector
is enabled and blocked with value 1.
11.4.34 Enable — After bus voltage recovery the device is
Options:
Enabled: The device is enabled and functions normally when the bus voltage is interrupted
or the device has been reprogrammed, as well as after a reset.
Blocked: The device is blocked and must be enabled for normal function when the bus
voltage is interrupted or the device has been reprogrammed, as well as after a reset.
11.4.35 Enable — Behaviour of output during enable
Options:
Control starts with the current output value: during enable it is checked whether a movement
has taken place. If yes, the lighting is switched on. If no, the lighting is switched off.
Control starts with switch-off value: during enable the single value which has been
parameterised under the value for switch-off parameter is sent.
KNX Technical Manual 2CKA001473B8667 │ 06.02.2017
Description of application and parameters
No
Yes
ON telegram
OFF telegram
Enabled
Blocked
Control starts at current output value
Control starts at switch-off value
Constant light switch application