11.8.107 Alarm functions — Frost alarm temperature for HVAC and RHCC status (°C)
Options:
The RHCC status and HVAC objects have a frost alarm bit. It the input temperature of the
controller drops below the temperature set in this parameter, then the frost alarm bit is set in the
status objects. It is reset when the temperature is exceeded.
11.8.108 Alarm functions — Heat alarm temperature for RHCC status (°C)
Options:
The RHCC status object has a heat alarm bit. If the input temperature of the controller exceeds
the temperature set in this parameter, then the heat alarm bit is set in the status object. It is
reset when the temperature falls below the set temperature.
KNX Technical Manual 2CKA001473B8667 │ 06.02.2017
Description of application and parameters
Setting options between 0 and 15
Setting options between 25 and 70
Application "RTC object"