Px: Saving Setpoint Brightness; Px: Actual Brightness; Px: Move/Adjust Blind; Px: Move Blind Into Position - Busch-Jaeger mini KNX 6131/20 series Technical Manual

Presence detector knx
Table of Contents

Advertisement

Communication objects — Presence detector — Constant light controller

11.16.11 Px: Saving setpoint brightness

Number
12 | 30
The desired brightness value is set with a control element via communication objects automatic
/ manual off, relative dimming (dimmer) and / or value (dimmer). If, for example, the luxmeter
shows the value 500 lx, this brightness value with the sending of a 1 will be stored on this
communication object as new setpoint of the control. Note: When setting the desired brightness,
e.g. 500 lx, the lamp's light-up time is to be taken into account.

11.16.12 Px: Actual brightness

Number
13 | 31
The current (filtered and corrected with daylight and constant light correction) brightness value
is made available via the "Actual brightness" communication object.

11.16.13 Px: Move/adjust blind

Number
14 | 32
The object is connected with the move command of the control element. When a value 1
(moving up) or 0 (moving down) is received, the parameters set under "Control parameters for
blind movement" become active. The switch mode is deactivated after a programmed time and
the normal control algorithm is reactivated.

11.16.14 Px: Move blind into position

Number
15 | 33
The object is connected with a 1-byte position command of the control element / actuator. When
a value is received, the parameters set under "Control parameters for blind movement" become
active. The switch mode is deactivated after a programmed time and the normal control
algorithm is reactivated.
KNX Technical Manual 2CKA001473B8667 │ 06.02.2017
Description of application and parameters
Name
Px: Saving setpoint brightness
Name
Px: Actual brightness
Name
Px: Move/adjust blind
Name
Px: Move blind into position
Object function
Input
Object function
Output
Object function
Input
Object function
Input
Data type
1.001 switch
Data type
9.* 2-byte float value
Data type
1.008 up/down
Data type
5.001 percentage
(0..100%)
│174