11.8.101 Temperature reading — Monitoring time for temperature reading (0 = no monitoring)
(min)
Options:
If no temperature is read within the parameterised time period, the device switches to error
mode. It transmits a telegram to the bus via the "Actual temperature error" object and applies
the operating mode and control value for error settings.
11.8.102 Temperature reading — Operating mode for fault
Options:
In the event of a failure of the actual temperature measurement, the device will no longer be
able to independently specify the heating/cooling operating type. As a result, the operating type
best suited to protecting the building will be selected.
Note
This parameter is only available when the "Control function" parameter is set to
"Heating and cooling" or "Heating and cooling with additional stage".
11.8.103 Temperature reading — Control value for fault (0 - 255)
Options:
In the event of a failure of the actual temperature measurement, the device will no longer be
able to independently determine the control value. Therefore, a control value which is suitable
for protecting the building will be selected.
KNX Technical Manual 2CKA001473B8667 │ 06.02.2017
Description of application and parameters
Setting option between 1 - 120
Cool
Heat
Setting option between 1 - 255