11.15.4 Px: slave

Number
The constant light switch can be switched on with a 1 from a different movement or presence
detector via the object.

11.15.5 Px: External brightness

Number
Via this object it is possible to link an external value from a different brightness sensor with the
constant light switch.

11.15.6 Px: Enable presence

Number
The constant light switch can be blocked or enabled via the object. Enabling has priority over all
other objects.

11.15.7 Px: Switch-off delay

Number
If no movement is detected, the function enters the programmed switch-off and then switches
off. The switch-off delay can be reprogrammed at all times via this object from a different control
element without the aid of ETS. If this value is not to be overwritten during each download, the
parameter "Overwrite setting during download" is to be programmed accordingly.

11.15.8 Px: Brightness-value threshold

Number
This communication object can be used to specify values from outside. This value is used as
the new switching threshold. The current switching threshold can be read via this
communication object. If this value is not to be overwritten during each download, the parameter
"Overwrite setting during download" is to be programmed accordingly.
KNX Technical Manual 2CKA001473B8667 │ 06.02.2017
Description of application and parameters
Communication objects — Presence detector — Constant light switch
Name
Px: Slave
Name
Px: External brightness
Name
Px: Enable presence
Name
Px: Switch-off delay
Name
Px: Brightness-value threshold
Object function
Object function
Object function
Object function
Object function
Data type
1.001 switch
Data type
9.* 2-byte float value
Data type
1.001 switch
Data type
7.005 time (s)
Data type
9.* 2-byte float value