Communication Objects - Presence Detector - Master; Px: Switchover Of Manual Operation; Px: External Push-Button; Px: Activate Test Mode - Busch-Jaeger mini KNX 6131/20 series Technical Manual

Presence detector knx
Table of Contents

Advertisement

11.12
Communication objects — Presence detector — Master

11.12.1 Px: switchover of manual operation

Number
12 | 30 | 48 |
64
This object is used to switch over from automatic mode to manual mode (default: 0 = automatic,
1 = manual).

11.12.2 Px: external push-button

Number
13 | 31 | 49 |
65
The detector switches on if a 1 (default) is received via this object. The detector switches off if a
0 (default) is received via this object.
Manual mode inactive: Movement detector is back on automatic.
Manual mode active: The movement detector remains switched off until the detector is
switched on manually or manual mode is deactivated.
Note
The movement detector is inactive in manual mode and to switch it on or off is
only possible only via the external push-button. In automatic mode the switch-on
via the external push-button simulates a movement.

11.12.3 Px: Activate test mode

Number
14 | 32 | 50 |
66
The test mode is activated via this object (1 = activated, 0 = deactivated). It is automatically
deactivated after 10 minutes.

11.12.4 Px: Brightness reduced according to switch-off delay

Number
16 | 34 | 52 |
68
If no movement is detected after the switch-off delay has expired, the function enters the
programmed switch-off delay and then switches off. The switch-off delay can be reprogrammed
at all times via this object from a different control element without the aid of ETS. If this value is
not to be overwritten during each download, the parameter "Overwrite setting during download"
is to be programmed accordingly.
KNX Technical Manual 2CKA001473B8667 │ 06.02.2017
Description of application and parameters
Communication objects — Presence detector — Master
Name
Px: switchover of manual
operation
Name
Px: external push-button
Name
Px: Activate test mode
Name
Px: Brightness reduced according
to switch-off delay
Object function
Input
Object function
Input
Object function
Input
Object function
Input
Data type
1.001 switch
Data type
1.001 switch
Data type
1.001 switch
Data type
7.005 time (s)
│165

Advertisement

Table of Contents
loading