Constant Light Switch Application; General Parameters - Output Is Of Type; General Parameters - Cyclic Sending Of Value For Switch-On - Busch-Jaeger mini KNX 6131/20 series Technical Manual

Presence detector knx
Table of Contents

Advertisement

11.4

Constant light switch application

11.4.1
General parameters — Output is of type
Options:
1 Bit: Intended for switch actuators.
1 Byte 0 - 100%: For activating dimmers.
1 Byte 0 - 255: For actuators, which are activated with a value of between 0 and 255.
Light scene number 1 - 64: For activating light scenes.
RTC operating mode switchover (1 Byte): To directly switch room temperature controllers
into a specific operating mode.
Auto
Comfort
Standby
ECO
Frost/heat protection
2-byte float: To send a specific temperature for example.
Note
If the type of output is changed, also the options for setting the parameters
change.
and when they are activated also for:
In this manual only values for the 1-bit setting are described.
11.4.2
General parameters — Cyclic sending of value for switch-on
Options:
No: The setpoint is sent only once via the bus.
Yes: The setpoint is sent cyclic via the bus.
Parameter "cyclic repeat time" is also displayed.
KNX Technical Manual 2CKA001473B8667 │ 06.02.2017
Description of application and parameters
1 bit
1 byte 0 - 100%
1 byte 0 - 255
Light scene number (1-64)
RTC operating mode switchover (1 byte)
2-byte float
Value for switch-on at output 1
Value for switch-off at output 1
Value for switch-on at output 2
Value for switch-off at output 2
No
Yes
Constant light switch application