Program Operation Method - Mitsubishi MR-JE-200A Instruction Manual

Mr-je series general-purpose interface ac servo. positioning mode
Hide thumbs Also See for MR-JE-200A:
Table of Contents

Advertisement

5. HOW TO USE THE PROGRAM
No.
Start-up sequence
4
Switch on ST1
Servo motor does not
(Forward rotation
rotate.
start).
5
Gain adjustment
Rotation ripples (speed
fluctuations) are large
at low speed.
Large load inertia
moment causes the
servo motor shaft to
oscillate side to side.
Note. Only a list of alarms and warnings is listed in chapter 8. Refer to "MELSERVO-JE Servo Amplifier Instruction Manual
(Troubleshooting)" for details of alarms and warnings.

5.2 Program operation method

5.2.1 Program operation method
Select a program created in advance on MR Configurator2 by using an input signal or communication, and
start an operation with ST1 (Forward rotation start).
This servo amplifier is set to the absolute value command method by factory setting.
For the position data, you can set the absolute value travel command ("MOV" command), which specifies
the target address, and the incremental value travel command ("MOVI" command), which specifies the travel
distance. Refer to section 4.2.1 (1) and 5.2.3 (1) (a) for the movable range and the setting unit.
Fault
Investigation
Check the on/off status of the
input signal with the external I/O
signal display (section 3.1.7).
Check [Pr. PA11 Forward rotation
torque limit] and [Pr. PA12
Reverse rotation torque limit].
When TLA (Analog torque limit)
is usable, check the input
voltage on the status display.
Make gain adjustment in the
following procedure.
1. Increase the auto tuning
response level.
2. Repeat acceleration and
deceleration several times to
complete auto tuning.
If the servo motor may be driven
with safety, repeat acceleration
and deceleration three times or
more to complete the auto
tuning.
5 - 6
Possible cause
LSP, LSN, and ST1 are off.
Torque limit level is too low for the
load torque.
Torque limit level is too low for the
load torque.
Gain adjustment fault
Gain adjustment fault
Reference
Section
3.1.7
Section
7.2.1
Section
3.1.2
MR-JE-_A
Chapter 6
MR-JE-_A
Chapter 6