Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 512

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Processing details
• These instructions transfer the 16-bit binary data in the device specified by (s) to the (n) points of the device specified by
(d).
b15
∙∙∙
b0
(s)
3456H
• When (s) is a word device and (d) is a bit device, the number of digit-specified bits in the word device is transferred.
Ex.
When K1Y30 is specified in (d), the lower 4 bits of the word device specified by (s) are transferred.
b15
∙∙∙
(s) D100
• When both (s) and (d) are bit devices, set the same number of digits for both devices.
Operation error
There is no operation error.
6 BASIC INSTRUCTIONS
510
6.7 Data Transfer Instructions
b15
∙∙∙
(d)
3456H
3456H
(d)+1
(d)+2
3456H
(d)+(n)-2
3456H
(d)+(n)-1
3456H
∙∙∙
b4
b3
b2
b1
b0
∙∙∙
Y3F
1
0
1
1
1
b0
(n)
(d)+3
(d)+2
(d)+1
(d)
∙∙∙ Y3C
Y3B
∙∙∙
Y38
Y37
∙∙∙
Y34
Y33
∙∙∙
Y30
0
1 1
1 0 1 1
1 0 1 1
1 0 1 1
(n)

Hide quick links:

Advertisement

Table of Contents
loading