Control Circuit Terminal Block - Toshiba VF-PS1 Instruction Manual

Variable torque inverter
Hide thumbs Also See for VF-PS1:
Table of Contents

Advertisement

2.3.2 Control circuit terminal block

The control circuit terminal block is common to all equipment.
⇒ How to set input terminal function, refer to section 7.
Terminal
Input/
Function (Sink logic)
symbol
output
VFPS1-****-WN
Shorting across F-CC causes forward
rotation; open causes deceleration
F
Input
stop. (Across PWR-P24/PLC is short
state.)
Shorting across R-CC causes reverse
rotation; open causes deceleration
R
Input
stop. (Across PWR-P24/PLC is short
state.)
Shorting and then opening RES-CC
cancels the status held by an inverter
RES
Input
protective function. When the inverter
is operating normally, shorting and then
opening RES-CC produces no effect.
Shorting across S1-CC causes preset
S1
Input
speed operation.
Shorting across S2-CC causes preset
S2
Input
speed operation.
Shorting across S3-CC causes preset
S3
Input
speed operation.
SW3: When SW3 is in the S4 position,
RR/S4 Input
S4 and CC are shorted and preset
speed operation is selected.
SW1=SINK (INT): Sink logic (When the
    
internal 24V power supply is used)
If SW1 is set to 1
P24/PLC
SW1
SINK
SOURCE
P24
2.2kΩ
2.2kΩ
CC
PWR-P24/PLC Shorting bar
Function (Source logic)
VFPS1-****-WP
Shorting across F-P24/PLC causes
forward rotation; open causes
deceleration stop. (Across PWR-
P24/PLC is short state.)
Shorting across R-P24/PLC causes
reverse rotation; open causes
deceleration stop. (Across PWR-
P24/PLC is short state.)
Shorting and then opening RES-
P24/PLC cancels the status held by an
inverter protective function. When the
inverter is operating normally, shorting
and then opening RES-P24/PLC
produces no effect.
Shorting across S1-P24/PLC causes
preset speed operation.
Shorting across S2-P24/PLC causes
preset speed operation.
Shorting across S3-P24/PLC causes
preset speed operation.
SW3: When SW3 is in the S4 position,
S4 and P24/PLC are shorted and preset
speed operation is selected.
SW1=SINK (PLC): Sink logic (When an
external 24V power supply is used)
If SW1 is set to 2
P24/PLC
SW1
SOURCE
SINK
P24
2.2kΩ
2.2kΩ
CC
B-11
E6581386
Electrical specifications
Voltage free contact
input
24Vdc-5mA or less
Lan current signal.
Choose low current
contacts to avoid
poor attaching.
*Sink/source selectable
with SW1
Sink input
ON:Less than DC10V
OFF:DC16V or more
Source input
ON:DC11V or more
OFF:Less than DC5V
Note:
Even when an
external power supply
is used (in sink logic
mode, i.e., when SINK
(PLC) is selected),
connect the reference
potential-side (0V
side) cable from the
power supply to the
CC terminal.
SW1=SOURCE (INT/PLC):
Source logic (When the internal 24V
power supply or an external 24V power
supply is used)
If SW1 is set to 3
2.2kΩ
2.2kΩ
P24
SINK
SOURCE
SW1
P24/PLC
CC
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents