Commissioning via the built-in BOP

5.7 Restoring to defaults

Setting parameter
Parameter
P0205
Function diagram
5.7
Restoring to defaults
Restoring to factory defaults
Parameter
Function
P0003
User access level
P0010
Commissioning parameter
P0970
Factory reset
Restoring to user defaults
Parameter
Function
P0003
User access level
P0010
Commissioning parameter
P0970
Factory reset
After setting the parameter P0970, the inverter displays "8 8 8 8 8" and then the screen
shows "P0970". P0970 and P0010 are automatically reset to their original value 0.
134
Function
Select inverter applications
Setting
= 1 (standard user access level)
= 30 (factory setting)
= 21: parameter reset to factory defaults deleting user defaults if
stored
Setting
= 1 (standard user access level)
= 30 (factory setting)
= 1: parameter reset to user defaults if stored, else factory de-
faults
Setting
This parameter selects the inverter applications on
high overload and low overload:
=0: high overload
=1: low overload
Operating Instructions, 11/2016, A5E34559884-006
SINAMICS V20 Inverter