Siemens SINAMICS V20 Operating Instructions Manual page 275

Hide thumbs Also See for SINAMICS V20:
Table of Contents

Advertisement

Parameter
Function
r2067.0...12
CO / BO: Digital input
values status
Displays status of digital inputs.
Bit
00
01
02
03
11
12
Note:
This is used for BICO connection without software intervention.
P2100[0...2]
Alarm number selection
Selects up to 3 faults or warnings for non-default reactions.
Example:
If, for example, an OFF3 is to be carried out instead of an OFF2 for a fault, the fault number has to be en-
tered in P2100 and the desired reaction selected in P2101 (in this case (OFF3) P2101 = 3).
Index:
[0]
[1]
[2]
Note:
All fault codes have a default reaction to OFF2.
Some fault codes caused by hardware trips (e.g. overcurrent) cannot be changed from the default reac-
tions.
SINAMICS V20 Inverter
Operating Instructions, 11/2016, A5E34559884-006
Range
-
Signal name
Digital input 1
Digital input 2
Digital input 3
Digital input 4
Digital input AI1
Digital input AI2
0 - 65535
Fault Number 1
Fault Number 2
Fault Number 3
Factory
Can be
default
changed
-
-
0
T
Parameter list
8.2 Parameter list
Scaling
Data
Data
set
type
-
-
U16
1 signal
0 signal
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
-
-
U16
Acc.
Level
3
3
275