Parameter
Boost type
P1312
Starting boost [%]
SINAMICS V20 Inverter
Operating Instructions, 11/2016, A5E34559884-006
Description
This parameter applies a constant linear offset relative to P0305 (rated motor
current) to active V/f curve (either linear or quadratic) after an ON command
and is active until:
ramp output reaches setpoint for the first time respectively
setpoint is reduced to less than present ramp output
Range: 0.0 to 250.0 (factory default: 0.0)
The voltage boost is only effective when accelerating for the first time (stand-
still).