Commissioning via the built-in BOP
5.5 Quick commissioning
Connection macro Cn004 - Fixed speeds in binary mode
Fixed speeds with ON command in binary mode
Up to 16 different fixed frequency values (0 Hz, P1001 to P1015) can be selected by the
fixed frequency selectors (P1020 to P1023).
Connection macro settings:
Parameter Description
P0700[0]
Selection of command source
P1000[0]
Selection of frequency
P0701[0]
Function of digital input 1
P0702[0]
Function of digital input 2
P0703[0]
Function of digital input 3
P0704[0]
Function of digital input 4
P1016[0]
Fixed frequency mode
P0840[0]
BI: ON/OFF1
P1020[0]
BI: Fixed frequency selection
bit 0
P1021[0]
BI: Fixed frequency selection
bit 1
P1022[0]
BI: Fixed frequency selection
bit 2
P1023[0]
BI: Fixed frequency selection
bit 3
P0771[0]
CI: Analog output
P0731[0]
BI: Function of digital output 1
P0732[0]
BI: Function of digital output 2
66
Factory default
Default for Cn004 Remarks
1
2
1
3
0
15
0
16
9
17
15
18
1
2
19.0
1025.0
722.3
722.0
722.4
722.1
722.5
722.2
722.6
722.3
21
21
52.3
52.2
52.7
52.3
Terminals as command source
Fixed frequency
Fixed speed bit 0
Fixed speed bit 1
Fixed speed bit 2
Fixed speed bit 3
Binary mode
Inverter starts at the fixed speed
selected
DI1
DI2
DI3
DI4
Actual frequency
Inverter running
Inverter fault active
SINAMICS V20 Inverter