Commissioning via the built-in BOP

5.2 Checking before power-on

5.2
Checking before power-on
Perform the following checks before you power on the inverter system:
● Check that all cables have been connected correctly and that all relevant product and
plant/location safety precautions have been observed.
● Ensure that the motor and the inverter are configured for the correct supply voltage.
● Tighten all screws to the specified tightening torque.
5.3

Setting the 50/60 Hz selection menu

Note
The 50/60 Hz selection menu is visible only on first power-up or after a factory reset (P0970).
You can make a selection using the BOP or exit the menu without making a selection, and
the menu will not be displayed unless a factory reset is performed.
The motor base frequency also can be selected by changing P0100 to the desired value.
Functionality
This menu is used to set the motor base frequency according to which region of the world
that the motor is used in. The menu determines whether power settings (for example, rated
motor power P0307) are expressed in [kW] or [hp].
Parameter
P0100
58
Value
Description
0
Motor base frequency is 50 Hz (default) → Europe [kW]
1
Motor base frequency is 60 Hz → United States/Canada [hp]
2
Motor base frequency is 60 Hz → United States/Canada [kW]
SINAMICS V20 Inverter
Operating Instructions, 11/2016, A5E34559884-006