Siemens SINAMICS V20 Operating Instructions Manual page 261

Hide thumbs Also See for SINAMICS V20:
Table of Contents

Advertisement

Parameter
Function
P1810
Control word Vdc control 0 - 3
Configures Vdc filtering and compensation.
Bit
00
01
Note:
P1810 default for the single phase variants is 2.
P1820[0...2]
Reverse output phase
sequence
Changes sequence of phases without changing setpoint polarity.
0
1
Note:
See P1000
P1825
On-state voltage of IGBT
[V]
Corrects on-state voltage of the IGBTs.
P1828
Gating unit dead time
[μs]
Sets compensation time of gating unit interlock.
P1900
Select motor data identi-
fication
Performs motor data identification.
0
2
Dependency:
No measurement if motor data incorrect.
P1900 = 2: Calculated value for stator resistance (see P0350) is overwritten.
Notice:
When the identification is finished P1900 is set to 0. When choosing the setting for measurement, observe
the following:
The value is actually adopted as P0350 parameter setting and applied to the control as well as being shown
in the read-only parameters below. Ensure that the motor holding brake is not active when performing the
motor identification.
Note:
Before selecting motor data identification, "Quick commissioning" has to be performed in advance.
Since the cable length of the applications differs in a wide range, the preset resistor P0352 is only a rough
estimation. Better results of the motor identification can be achieved by specifying the cable resistor before
the start of the motor identification by measuring / calculating.
Once enabled (P1900 > 0), A541 generates a warning that the next ON command will initiate measurement
of motor parameters.
Communications - both via USS as well as via the Modbus - are interrupted for the time that it takes to
make internal calculations. These calculations can take up to one minute to complete.
P1909[0...2]
Control word of motor
data identification
Control word of motor data identification.
Bit
00
01
SINAMICS V20 Inverter
Operating Instructions, 11/2016, A5E34559884-006
Range
Signal name
Enable Vdc average filter
Enable Vdc compensation
0 - 1
Forward
Reverse the Motor
0.0 - 20.0
0.00 - 3.98
0 - 2
Disabled
Identification of all parameters in standstill
0 - 65519
Signal name
Estimation of Xs
Motor ID at 2 kHz
Factory
Can be
default
changed
3
U, T
0
T
0.9
U, T
0.01
U, T
0
C, T
23552
U, T
Parameter list
8.2 Parameter list
Scaling
Data
Data
set
type
-
-
U16
1 signal
0 signal
Yes
No
Yes
No
-
DDS
U16
-
-
Float
-
-
Float
-
-
U16
-
DDS
U16
1 signal
0 signal
Yes
No
Yes
No
Acc.
Level
3
2
4
4
2
4
261