Connection macro Cn003 - Fixed speeds
Three fixed speeds with ON/OFF1
If more than one fixed frequency is selected at the same time, the selected frequencies are
summed, that is, FF1 + FF2 + FF3.
Connection macro settings:
Parameter Description
P0700[0]
Selection of command source
P1000[0]
Selection of frequency
P0701[0]
Function of digital input 1
P0702[0]
Function of digital input 2
P0703[0]
Function of digital input 3
P0704[0]
Function of digital input 4
P1016[0]
Fixed frequency mode
P1020[0]
BI: Fixed frequency selection
bit 0
P1021[0]
BI: Fixed frequency selection
bit 1
P1022[0]
BI: Fixed frequency selection
bit 2
P1001[0]
Fixed frequency 1
P1002[0]
Fixed frequency 2
P1003[0]
Fixed frequency 3
P0771[0]
CI: Analog output
P0731[0]
BI: Function of digital output 1
P0732[0]
BI: Function of digital output 2
SINAMICS V20 Inverter
Operating Instructions, 11/2016, A5E34559884-006
Factory default
Default for Cn003
1
2
1
3
0
1
0
15
9
16
15
17
1
1
722.3
722.1
722.4
722.2
722.5
722.3
10
10
15
15
25
25
21
21
52.3
52.2
52.7
52.3
Commissioning via the built-in BOP
5.5 Quick commissioning
Remarks
Terminal as command source
Fixed frequency
ON/OFF
Fixed speed bit 0
Fixed speed bit 1
Fixed speed bit 2
Direct selection mode
DI2
DI3
DI4
Speed low
Speed middle
Speed high
Actual frequency
Inverter running
Inverter fault active