FC6 - Write Single Register
When a message with FC = 0x06 is received, then 4 bytes of data are expected, that is, FC6
has 4 bytes of data:
● 2 bytes for the starting address of register
● 2 bytes for the register value
Byte 1
Byte 2
Address
FC (0x06)
Inverter response
Byte 1
Byte 2
Address
FC (0x06)
FC16 - Write Multiple Registers
When a message with FC = 0x10 is received, then 5 + N bytes of data are expected, that is,
FC16 has 5 + N bytes of data:
● 2 bytes for the starting address of register
● 2 bytes for the number of registers
● 1 byte for the byte count
● N bytes for the register values
Byte 1
Byte 2
Byte 3
Address FC
Start address
(0x10)
High
Inverter response
Byte 1
Byte 2
Address
FC (0x10)
SINAMICS V20 Inverter
Operating Instructions, 11/2016, A5E34559884-006
Byte 3
Byte 4
Start address
High
Low
Byte 3
Byte 4
Start address
High
Low
Byte 4
Byte 5
Byte 6
Number of regis-
ters
Low
High
Low
Byte 3
Byte 4
Start address
High
Low
Byte 5
Byte 6
New register value
High
Low
Byte 5
Byte 6
New register value
High
Low
Byte 7
...
Byte N -
1
Number
...
Register N value
of bytes
High
Byte 5
Byte 6
Number of registers
High
Low
Communicating with the PLC
7.2 MODBUS communication
Byte 7
Byte 8
CRC
High
Low
Byte 7
Byte 8
CRC
High
Low
Byte N
Byte N +
Byte N +
1
2
CRC
Low
High
Low
Byte 7
Byte 8
CRC
High
Low
171