Parameter list
8.2 Parameter list
Parameter
Function
P0703[0...2]
Function of digital input 3 0 - 99
Selects function of digital input 3.
See P0701.
P0704[0...2]
Function of digital input 4 0 - 99
Selects function of digital input 4.
See P0701.
P0712[0...2]
Analog / digital input 1
Selects function of digital input AI1 (via analog input).
See P0701.
Note:
See P0701. Signals above 4 V are active; signals below 1.6 V are inactive.
P0713[0...2]
Analog / digital input 2
Selects function of digital input AI2 (via analog input).
See P0701.
Note:
See P0701. Signals above 4 V are active; signals below 1.6 V are inactive.
P0717
Connection macro
Selects a given connection macro, which is a set of parameter values for a given set of control connections.
There are a number of connection macros which define basic control connection settings such as Termi-
nals, BOP, PID with analog setpoint etc.
Note:
Please note that to guarantee correct setting of the Connection macro, the Connection macro number
should only be changed during Setup directly after a parameter reset.
P0719[0...2]
Selection of command &
frequency setpoint
Central switch to select control command source for inverter. Switches command and setpoint source be-
tween freely programmable BICO parameters and fixed command / setpoint profiles. Command and set-
point sources can be changed independently. The tens digit chooses the command source and the units
digit chooses the setpoint source.
0
1
2
3
4
5
7
40
41
42
43
44
45
47
50
51
52
212
Range
Factory
default
9
15
0 - 99
0
0 - 99
0
0 - 255
0
0 - 57
0
Cmd = BICO parameter, Setpoint = BICO parameter
Cmd = BICO parameter, Setpoint = MOP setpoint
Cmd = BICO parameter, Setpoint = Analog setpoint
Cmd = BICO parameter, Setpoint = Fixed frequency
Cmd = BICO parameter, Setpoint = USS on RS232 (reserved)
Cmd = BICO parameter, Setpoint = USS/MODBUS on RS485
Cmd = BICO parameter, Setpoint = Analog setpoint 2
Cmd = USS on RS232 (reserved), Setpoint = BICO parameter
Cmd = USS on RS232 (reserved), Setpoint = MOP setpoint
Cmd = USS on RS232 (reserved), Setpoint = Analog setpoint
Cmd = USS on RS232 (reserved), Setpoint = Fixed frequency
Cmd = USS on RS232 (reserved), Setpoint = USS on RS232 (reserved)
Cmd = USS on RS232 (reserved), Setpoint = USS/MODBUS on RS485
Cmd = USS on RS232 (reserved), Setpoint = Analog setpoint 2
Cmd = USS/MODBUS on RS485, Setpoint = BICO parameter
Cmd = USS/MODBUS on RS485, Setpoint = MOP setpoint
Cmd = USS/MODBUS on RS485, Setpoint = Analog setpoint
Can be
Scaling
changed
T
-
T
-
T
-
T
-
C(1)
-
T
-
Operating Instructions, 11/2016, A5E34559884-006
Data
Data
Acc.
set
type
Level
CDS
U16
2
CDS
U16
2
CDS
U16
2
CDS
U16
2
-
U16
1
CDS
U16
4