Options and spare parts
B.1 Options
Transferring data from SD card to inverter
There are two ways to perform a data transfer.
Method 1:
(Precondition: Inverter is to be powered up after inserting the card)
1. Fit the option module to the inverter.
2. Insert the card into the option module. Make sure the card contains the file "clone00.bin".
3. Power on the inverter.
Data transfer starts automatically. Then the fault code F395 displays which means
"Cloning has occurred. Do you want to keep the clone edits?".
4. To save the clone edits, press
written to EEPROM, the LED is lit up orange and flashes at 1Hz.
If you do not wish to keep the clone edits, remove the card or the option module and
restart the inverter. The inverter will power up with the fault code F395 (r0949 = 10)
indicating that the previous cloning was aborted. To clear the fault code, press
Method 2:
(Precondition: Inverter is powered up before inserting the card)
1. Fit the option module to the powered inverter.
2. Insert the card into the option module.
3. Set P0003 (user access level) = 3.
4. Set P0010 (commissioning parameter) = 30.
5. Set P0804 (select clone file). This step is necessary only when the card does not contain
the file "clone00.bin". The inverter copies by default the file "clone00.bin" from the card.
6. Set P0803 (transfer data from card to inverter) = 2 or 3.
The inverter displays "8 8 8 8 8" during transfer and the LED is lit up orange and flashes at 1
Hz. After a successful transfer, both P0010 and P0803 are automatically reset to 0.
Note that fault code F395 only occurs with power-up cloning.
B.1.2

External BOP and BOP Interface Module

External BOP
Article number: 6SL3255-0VA00-4BA1
The external BOP is used for remote control of the inverter operation. When mounted on a
suitable cabinet door, the external BOP can achieve a UL/cUL Type 1 enclosure rating.
Components
● External BOP unit
● 4 x M3 screws
348
and the fault code is cleared. When the clone file is
Operating Instructions, 11/2016, A5E34559884-006
.
SINAMICS V20 Inverter