Parameter list
8.2 Parameter list
Parameter
Function
Note:
When using the setpoint source
Analog Input
USS
the setpoint frequency (in Hz) is cyclically calculated using
a percentage value(e.g. for the analog input r0754)
a hexadecimal value (e.g. for the USS r2018[1])
and the reference frequency P2000.
If for example P1082 = 80 Hz, P2000 = 50 Hz and the analog input is parameterized with P0757 = 0 V,
P0758 = 0 %, P0759 = 10 V, P0760 = 100 %, a setpoint frequency of 50 Hz will be applied at 10 V of the
analog input. When Quick Commissioning is carried out P2000 is changed as follows: P2000 = P1082.
r1084
Resultant maximum
frequency [Hz]
Displays resultant maximum frequency.
P1091[0...2]
Skip frequency [Hz]
Defines skip frequency 1 which avoids effects of mechanical resonance and suppresses frequencies with-
in + / -P1101 (skip frequency bandwidth).
Notice:
Stationary operation is not possible within the suppressed frequency range; the range is merely passed
through (on the ramp). For example, if P1091 = 10 Hz and P1101 = 2 Hz, it is not possible to operate
continuously between 10 Hz + / - 2 Hz (i.e. between 8 and 12 Hz).
Note:
The function is disabled if P1091 = 0.
P1092[0...2]
Skip frequency 2 [Hz]
Defines skip frequency 2 which avoids effects of mechanical resonance and suppresses frequencies with-
in + / -P1101 (skip frequency bandwidth).
Note:
See P1091
P1093[0...2]
Skip frequency 3 [Hz]
Defines skip frequency 3 which avoids effects of mechanical resonance and suppresses frequencies with-
in + / -P1101 (skip frequency bandwidth).
Note:
See P1091
P1094[0...2]
Skip frequency 4 [Hz]
Defines skip frequency 4 which avoids effects of mechanical resonance and suppresses frequencies with-
in + / -P1101 (skip frequency bandwidth).
Note:
See P1091
P1101[0...2]
Skip frequency band-
width [Hz]
Delivers frequency bandwidth to be applied to skip frequencies.
Note:
See P1091
P1110[0...2]
BI: Inhibit negative fre-
quency setpoint
This parameter suppresses negative setpoints. Therefore, modification of the motor direction is inhibited
to the set-point channel. If a minimum frequency (P1080) and a negative setpoint are given, the motor is
accelerated by a positive value in relationship to the minimum frequency.
Setting:
0
1
240
Range
Factory de-
fault
-
-
0.00 - 550.00 0.00
0.00 - 550.00 0.00
0.00 - 550.00 0.00
0.00 - 550.00 0.00
0.00 - 10.00
2.00
0 -
0
4294967295
Disabled
Enabled
Can be
Scaling
Data
changed
set
-
-
-
U, T
-
DDS
U, T
-
DDS
U, T
-
DDS
U, T
-
DDS
U, T
-
DDS
T
-
CDS
Operating Instructions, 11/2016, A5E34559884-006
Data
Acc.
type
Level
Float
3
Float
3
Float
3
Float
3
Float
3
Float
3
U32
3
SINAMICS V20 Inverter

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents