Parameter list
8.2 Parameter list
Parameter
Function
P0350[0...2]
Stator resistance (line)
[Ω]
Stator resistance value for connected motor (line value). The parameter value doesn't include the cable
resistance.
Dependency:
See P0341
Note:
There are three ways to determine the value for this parameter:
Calculate using
P0340 = 1 (data entered from rating plate) or
P0010 = 1, P3900 = 1, 2 or 3 (end of quick commissioning).
Measure using P1900 = 2 (standard motor data identification - value for stator resistance is overwrit-
ten).
Measure manually using an Ohmmeter.
Since the manually measured resistor is a line-to-line value, which includes the cable resistors, the meas-
ured value has to be divided by two and the cable resistor of a line has to be subtracted from that value.
The value entered in P0350 is the one obtained by the method last used. Default value is depending on
inverter type and its rating data.
P0352[0...2]
Cable resistance [Ω]
Describes cable resistance between inverter and motor for one phase. The value corresponds to the re-
sistance of the cable between the inverter and the motor, relative to the rated impedance.
Dependency:
See P0341
P0354[0...2]
Rotor resistance [Ω]
Sets rotor resistance of motor equivalent circuit (phase value).
Dependency:
Calculated automatically using the motor model or determined using P1900 (motor identification). This
parameter is influenced by automatic calculations defined by P0340.
P0356[0...2]
Stator leakage induct-
ance [mH]
Sets stator leakage inductance of motor equivalent circuit (phase value).
Dependency:
See P0354
P0358[0...2]
Rotor leakage induct-
ance [mH]
Sets rotor leakage inductance of motor equivalent circuit (phase value).
Dependency:
See P0354
P0360[0...2]
Main inductance [mH]
Sets main inductance of the motor equivalent circuit (phase value).
Dependency:
See P0354
Caution:
The data of equivalent circuit relates to the star equivalent circuit. Any data of the delta equivalent circuit
available therefore must be transformed to the star equivalent circuit before entering into the inverter.
r0370[0...2]
Stator resistance [%]
Displays standardized stator resistance of motor equivalent circuit (phase value).
r0372[0...2]
Cable resistance [%]
Displays standardized cable resistance of motor equivalent circuit (phase value). It is estimated to be
20 % of the stator resistance.
r0373[0...2]
Rated stator resistance
[%]
Displays rated stator resistance of the motor equivalent circuit (phase value).
206
Range
Factory
default
0.00001 -
2.0000
2000.0
0.0 - 120.0
0.0
0.0 - 300.0
10.0
0.00001 -
10.000
1000.0
0.0 - 1000.0
10.0
0.0 - 10000.0
10.0
-
-
-
-
-
-
Can be
Scaling
changed
U, T
-
U, T
-
U, T
-
U, T
-
U, T
-
U, T
-
-
PERCENT
-
PERCENT
-
PERCENT
Operating Instructions, 11/2016, A5E34559884-006
Data
Data
Acc.
set
type
Level
DDS
Float
3
DDS
Float
3
DDS
Float
3
DDS
Float
3
DDS
Float
3
DDS
Float
3
DDS
Float
4
DDS
Float
4
DDS
Float
4
SINAMICS V20 Inverter