Siemens SINAMICS V20 Operating Instructions Manual page 103

Hide thumbs Also See for SINAMICS V20:
Table of Contents

Advertisement

Setting ramp-up / down rounding time
Rounding times are recommended, since they prevent an abrupt response, thus avoiding
detrimental effects on the mechanics.
Rounding times are not recommended when analog inputs are used, since they would result
in overshoot / undershoot in the inverter response.
Setting parameters
Parameter
Function
P1130[0...2]
Ramp-up initial rounding time [s]
P1131[0...2]
Ramp-up final rounding time [s]
P1132[0...2]
Ramp-down initial rounding time [s]
P1133[0...2]
Ramp-down final rounding time [s]
SINAMICS V20 Inverter
Operating Instructions, 11/2016, A5E34559884-006
Commissioning via the built-in BOP
Setting
This parameter defines rounding time at start of ramp-up.
Range: 0.00 to 40.00 (factory default: 0.00)
This parameter defines rounding time at end of ramp-up.
Range: 0.00 to 40.00 (factory default: 0.00)
This parameter defines rounding time at start of ramp-down.
Range: 0.00 to 40.00 (factory default: 0.00)
This parameter defines rounding time at end of ramp-down.
Range: 0.00 to 40.00 (factory default: 0.00)
5.6 Function commissioning
103

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents