Communicating with the PLC
7.1 USS communication
Error numbers in response ID 7 (request cannot be processed)
No.
Description
0
Illegal PNU (illegal parameter number; parameter number not available)
1
Parameter value cannot be changed (parameter is read-only)
2
Lower or upper limit violated (limit exceeded)
3
Wrong sub-index
4
No array
5
Wrong parameter type/incorrect data type
6
Setting is not allowed (parameter value can only be reset to zero)
7
The descriptive element is not changeable and can only be read
9
Descriptive data not available
10
Access group incorrect
11
No parameter change rights. See parameter P0927. Must have status as master control.
12
Incorrect password
17
The current inverter operating status does not permit the request processing
18
Other error
20
Illegal value. Change request for a value which is within the limits, but it is not allowed for other reasons (pa-
rameter with defined single values)
101
Parameter is currently deactivated; parameter has no function in the present inverter status
102
Communication channel width is insufficient for response; dependent on the number of PKW and the maximum
net data length of the inverter
104
Illegal parameter value
105
Parameter is indexed
106
Request is not included/task is not supported
109
PKW request access timeout/number of retries is exceeded/wait for response from CPU side
110
Parameter value cannot be changed (parameter is locked)
200/201
Changed lower/upper limits exceeded
202/203
No display on the BOP
204
The available access authorization does not cover parameter changes
300
Array elements differ
Basic inverter settings
Parameter
Function
P0010
Commissioning parameter
P0970
Factory reset
P0003
User access level
168
Setting
= 30: restores to factory settings
Possible settings:
= 1: resets all parameters (not user defaults) to their default
values
= 21: resets all parameters and all user defaults to factory
reset state
Note: Parameters P2010, P2011, P2023 retain their values
after a factory reset.
= 3