P0810
BI: command data set bit
0 (Hand / Auto)
Selects command source from which to read Bit 0 for selecting a command data set (CDS). The actual
selected CDS is displayed in r0054.15 (CDS bit 0) and r0055.15 (CDS bit 1). The actual active CDS is
displayed in r0050.
Setting:
722.0
722.1
722.2
Note:
P0811 is also relevant for command data set (CDS) selection.
P0811
BI: command data set bit
1
Selects command source from which to read Bit 1 for selecting a command data set (see P0810).
Setting:
See P0810.
Note:
P0810 is also relevant for command data set (CDS) selection.
P0819[0...2]
Copy inverter data set
(DDS)
Calls 'Copy inverter data set (DDS)' function. The list of all inverter data set (DDS) parameters is shown in
"Index" at the end of the manual.
Example:
Copying of all values from DDS0 to DDS2 can be accomplished by the following procedure:
P0819[0] = 0 Copy from DDS0
P0819[1] = 2 Copy to DDS2
P0819[2] = 1 Start copy
Index:
[0]
[1]
[2]
Note:
See P0809
P0820
BI: inverter data set bit 0
Selects command source from which to read Bit 0 for selecting an inverter data set (DDS). The actual
selected inverter data set (DDS) is displayed in parameter r0051[0]. The actual active inverter data set
(DDS) is displayed in parameter r0051[1].
Setting:
See P0810
Note:
P0821 is also relevant for inverter data set (DDS) selection.
P0821
BI: inverter data set bit 1
Selects command source from which Bit 1 for selecting an inverter data set is to be read in (see P0820).
Setting:
See P0810
Note:
P0820 is also relevant for inverter data set (DDS) selection.
P0840[0...2]
BI: ON / OFF1
Allows ON / OFF1 command source to be selected using BICO. The digits in front of the colon show the
parameter number of the command source; the digits following the colon denote the bit setting for that
parameter.
Setting:
See P0810
SINAMICS V20 Inverter
Operating Instructions, 11/2016, A5E34559884-006
Range
Factory
default
0 -
0
4294967295
Digital input 1 (requires P0701 to be set to 99, BICO)
Digital input 2 (requires P0702 to be set to 99, BICO)
Digital input 3 (requires P0703 to be set to 99, BICO)
0 -
0
4294967295
0 - 2
[0] 0
[1] 1
[2] 0
Copy from DDS
Copy to DDS
Start copy
0 -
0
4294967295
0 -
0
4294967295
0 -
19.0
4294967295
Can be
Scaling
Data
changed
set
U, T
-
-
U, T
-
-
T
-
-
T
-
-
T
-
-
T
-
CDS
Parameter list
8.2 Parameter list
Data
Acc.
type
Level
U32
2
U32
2
U16
2
U32
3
U32
3
U32
3
223