Setting parameters
You only have to change the factory default settings of the Imax controller if the inverter
tends to oscillate when it reaches the current limit or it is shut down due to overcurrent.
Parameter
Function
P0305[0...2]
Rated motor current [A]
P0640[0...2]
Motor overload factor [%]
P1340[0...2]
Imax controller proportional gain
P1341[0...2]
Imax controller integral time [s]
P1345[0...2]
Imax voltage controller proportional
gain
P1346[0...2]
Imax voltage controller integral time
[s]
r0056.13
Status of motor control: Imax controller active
SINAMICS V20 Inverter
Operating Instructions, 11/2016, A5E34559884-006
Commissioning via the built-in BOP
Setting
This parameter defines the nominal motor current from rating
plate.
This parameter defines motor overload current limit relative to
P0305 (rated motor current).
This parameter defines the proportional gain of the Imax con-
troller.
Range: 0.000 to 0.499 (factory default: 0.030)
This parameter defines the integral time constant of the Imax
controller. Setting P1341 to 0 disables the Imax controller.
Range: 0.000 to 50.000 (factory default: 0.300)
This parameter sets the proportional gain of Imax voltage
controller. If the output current (r0068) exceeds the maximum
current (r0067), the inverter is dynamically controlled by re-
ducing the output voltage.
Range: 0.000 to 5.499 (factory default: 0.250)
This parameter defines the integral time constant of the Imax
voltage controller.
Range: 0.000 to 50.000 (factory default: 0.300)