Parameter
Function
P1140[0...2]
BI: RFG enable
Defines command source of RFG enable command (RFG: ramp function generator). If binary input is
equal to zero then the RFG output will be set immediately to 0.
P1141[0...2]
BI: RFG start
Defines command source of RFG start command (RFG: ramp function generator). If binary input is equal
to zero then the RFG output is held at its present value.
P1142[0...2]
BI: RFG enable setpoint
Defines command source of RFG enable setpoint command (RFG: ramp function generator). If binary
input is equal to zero, the RFG input will be set to zero and the RFG output will ramp-down to zero.
r1170
CO: Frequency setpoint
after RFG [Hz]
Displays overall frequency setpoint after ramp generator.
P1175[0...2]
BI: Dual ramp enable
Defines command source of dual ramp enable command. If binary input is equal to one, then the dual
ramp will be applied. This works as follows:
Ramp-up:
Inverter starts ramp-up using ramp time from P1120
When f_act > P2157, switch to ramp time from P1060
Ramp-down:
Inverter starts ramp-down using ramp time from P1061
When f_act < P2159, switch to ramp time from P1121
SINAMICS V20 Inverter
Operating Instructions, 11/2016, A5E34559884-006
Range
Factory de-
fault
0 -
1
4294967295
0 -
1
4294967295
0 -
1
4294967295
-
-
0 -
0
4294967295
Can be
Scaling
Data
changed
set
T
-
CDS
T
-
CDS
T
-
CDS
-
-
-
T
-
CDS
Parameter list
8.2 Parameter list
Data
Acc.
type
Level
U32
3
U32
3
U32
3
Float
3
U32
3
243

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents