Parameter
Function
r0017
CO / BO: BOP button
status
Shows the immediate status of the BOP buttons.
Bit
00
01
02
03
05
06
07
Note:
Bit 07 (ON/OFF), will remain high if the run button has been pressed and released. It will only be reset
once the stop button has been pressed.
r0018
Firmware version
Displays version number of installed firmware.
r0019.0...14
CO / BO: Operator
panel control word
Displays status of operator panel commands. The settings below are used as the "source" codes for key-
pad control when connecting to BICO input parameters.
Bit
00
01
08
11
13
14
Note:
When BICO technology is used to allocate functions to panel buttons, this parameter displays the actual
status of the relevant command.
r0020
CO: Frequency set-
point before RFG [Hz]
Displays actual frequency setpoint (input of ramp function generator). This value is available filtered
(r0020) and unfiltered (r1119). The actual frequency setpoint after RFG is displayed in r1170.
r0021
CO: Actual filtered
frequency [Hz]
Displays actual inverter output frequency (r0024) excluding slip compensation (and resonance damping,
frequency limitation in V/f mode).
r0022
Actual filtered rotor
speed [RPM]
Displays calculated rotor speed based on r0021 (filtered output frequency [Hz] x 120 / number of poles).
The value is updated every 128 ms.
Note:
This calculation makes no allowance for load-dependent slip.
r0024
CO: Actual filtered
output frequency [Hz]
Displays actual filtered output frequency (slip compensation, resonance damping and frequency limitation
are included). See also r0021. This value is available filtered (r0024) and unfiltered (r0066).
SINAMICS V20 Inverter
Operating Instructions, 11/2016, A5E34559884-006
Range
-
Signal name
Run button
Stop button
HAND/AUTO button combination (OK + M)
OK button
Up button
Down button
Run/stop latch
-
-
Signal name
ON / OFF1
OFF2: Electrical stop
JOG right
Reverse (setpoint inversion)
Motor potentiometer MOP up
Motor potentiometer MOP down
-
-
-
-
Factory
Can be
default
changed
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Parameter list
8.2 Parameter list
Scaling
Data
Data
set
type
-
-
U16
1 signal
0 signal
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
-
-
Float
-
-
U16
1 signal
0 signal
Yes
No
No
Yes
Yes
No
Yes
No
Yes
No
Yes
No
-
-
Float
-
-
Float
-
-
Float
-
-
Float
Acc.
Level
3
1
3
3
2
3
3
187