Mode "Std Didd; Namur Mode Settings; Operation According To Namur Defaults - Siemens SINAMICS G180 Installation And Operating Instructions Manual

Inverters - compact units, cabinet systems, cabinet units air and liquid cooled
Hide thumbs Also See for SINAMICS G180:
Table of Contents

Advertisement

Operation

8.3 NAMUR mode settings

8.2.4

Mode "std didd"

(D)
(S)
Figure 8-6
Operation different from "std dids"
The operation "Speed On" for "Remote" mode is dynamic.
Start the drive with an NO (normally open) contact at -X2:11. Change the inverter speed to 0
with an NC (normally closed) contact at -X2:10.
8.3
NAMUR mode settings
8.3.1

Operation according to NAMUR defaults

If you activate the control cable terminal -X2:9 with 24 V, then the operating source and the
setpoint input are switched from "Test" to "Normal" using a parameter switch.
You can connect the up and down buttons of a motor potentiometer function to control cable
terminals -X2:12 and -X2:13. If you would like to use the motor potentiometer, you must also
under "P-PARAMETER SWITCH/AV" change the setting of bit "AI 1" for analog setpoint
value 1 to "MPoti". The motor potentiometer function is now valid in "Normal" mode and not
valid in test mode.
"Reset" (NO): Reset faults and "fast stop" using a 24 V pulse at -X2:14.
138
Dynamic: Pushbutton mode
Static: Switch mode
Assignment of the control cable terminals for "std didd" mode
Installation and Operating Instructions SINAMICS G180
Operating Instructions, 02/2019, 4BS0751-007

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents