Parameter
Function
P2268
Minimum value for PID
feedback [%]
Sets lower limit for value of feedback signal.
Notice:
When PID is enabled (P2200 = 1) and the signal drops below this value, the inverter will trip with F221.
Note:
P2268 = 100 % corresponds to 4000 hex.
P2269
Gain applied to PID
feedback
Allows the user to scale the PID feedback as a percentage value. A gain of 100.0 % means that feedback
signal has not changed from its default value.
P2270
PID feedback function
selector
Applies mathematical functions to the PID feedback signal, allowing multiplication of the result by P2269.
0
1
2
3
P2271
PID transducer type
Allows the user to select the transducer type for the PID feedback signal.
0
1
Notice:
It is essential that you select the correct transducer type. If you are unsure whether 0 or 1 is applicable, you
can determine the correct type as follows:
1. Disable the PID function (P2200 = 0).
2. Increase the motor frequency while measuring the feedback signal.
3. If the feedback signal increases with an increase in motor frequency, the PID transducer type should be
0.
4. If the feedback signal decreases with an increase in motor frequency the PID transducer type should be
set to 1.
r2272
CO: PID scaled feed-
back [%]
Displays PID scaled feedback signal.
Note:
r2272 = 100 % corresponds to 4000 hex.
r2273
CO: PID error [%]
Displays PID error (difference) signal between setpoint and feedback signals.
Note:
r2273 = 100 % corresponds to 4000 hex.
P2274
PID derivative time [s]
Sets PID derivative time.
P2274 = 0: The derivative term does not have any effect (it applies a gain of 1).
P2280
PID proportional gain
Allows user to set proportional gain for PID controller. The PID controller is implemented using the standard
model. For best results, enable both P and I terms.
Dependency:
P2280 = 0 (P term of PID = 0): The I term acts on the square of the error signal.
P2285 = 0 (I term of PID = 0): PID controller acts as a P or PD controller respectively.
SINAMICS V20 Inverter
Operating Instructions, 11/2016, A5E34559884-006
Range
Factory
default
-200.00 - 200.00 0.00
0.00 - 500.00
100.00
0 - 3
0
Disabled
Square root (root(x))
Square (x*x)
Cube (x*x*x)
0 - 1
0
Disabled
Inversion of PID feedback signal
-
-
-
-
0.000 - 60.000
0.000
0.000 - 65.000
3.000
Can be
Scaling
changed
U, T
-
U, T
-
U, T
-
U, T
-
-
-
-
-
U, T
-
U, T
-
Parameter list
8.2 Parameter list
Data
Data
Acc.
set
type
Level
-
Float
3
-
Float
3
-
U16
3
-
U16
2
-
Float
2
-
Float
2
-
Float
2
-
Float
2
289