Parameter
Function
r0752[0...1]
Actual analog input [V]
or [mA]
Displays smoothed analog input value in volts or million amps before the scaling block.
Index:
[0]
[1]
P0753[0...1]
Smooth time analog
input [ms]
Defines filter time (PT1 filter) for analog input.
Index:
See r0752
Note:
Increasing this time (smooth) reduces jitter but slows down response to the analog input.
P0753 = 0: No filtering
r0754[0...1]
Actual analog input val-
ue after scaling [%]
Shows smoothed value of analog input after scaling block.
Index:
See r0752
Dependency:
P0757 to P0760 define range (analog input scaling).
r0755[0...1]
CO: Actual analog input
after scaling [4000h]
Displays analog input, scaled using ASPmin and ASPmax (ASP = analog setpoint).
Analog setpoint (ASP) from the analog scaling block can vary from minimum analog setpoint (ASPmin) to a
maximum analog setpoint (ASPmax).
The largest magnitude (value without sign) of ASPmin and ASPmax defines the scaling of 16384.
By associating r0755 with an internal value (e.g. frequency setpoint), a scaled value is calculated internally
by the inverter.
The frequency value is calculated using the following equation:
r0755 [Hz] = (r0755 [hex] / 4000 [hex]) * P2000 * (max (|ASP_max|, |ASP_min|) / 100%)
Example:
Case a:
ASPmin = 300 %, ASPmax = 100 % then 16384 represents 300 %.
This parameter will vary from 5461 to 16384.
Case b:
ASPmin = -200 %, ASPmax = 100 % then 16384 represents 200 %.
This parameter will vary from -16384 to +8192.
SINAMICS V20 Inverter
Operating Instructions, 11/2016, A5E34559884-006
Range
Factory
default
-
-
Analog input 1 (AI1)
Analog input 2 (AI2)
0 - 10000
3
-
-
-
-
Can be
Scaling
changed
-
-
U, T
-
-
-
-
4000H
Parameter list
8.2 Parameter list
Data
Data
Acc.
set
type
Level
-
Float
2
-
U16
3
-
Float
2
-
I16
2
217