Running The Inverter In Jog Mode - Siemens SINAMICS V20 Operating Instructions Manual

Hide thumbs Also See for SINAMICS V20:
Table of Contents

Advertisement

OFF3
The braking characteristics of OFF3 are identical with those of OFF1 with the exception of
the independent OFF3 ramp-down time P1135. If the output frequency falls below parameter
value P2167 and if the time in P2168 has expired, then the inverter pulses are cancelled as
for the OFF1 command.
Note
• OFF3 can be entered using a wide range of command sources via BICO parameters
P0848 (BI: 1. OFF3) and P0849 (BI: 2. OFF3).
• OFF3 is active low.
• When various OFF commands are selected simultaneously, the following priority applies:
OFF2 (highest priority) – OFF3 – OFF1
5.6.2.2

Running the inverter in JOG mode

Functionality
The JOG function can be controlled by either the (built-in) BOP or the digital inputs. When
controlled by the BOP, pressing the RUN button will cause the motor to start and rotate at
the pre-set JOG frequency (P1058). The motor stops when the RUN button is released.
When using the digital inputs as the JOG command source, the JOG frequency is set by
P1058 for JOG right and P1059 for JOG left.
SINAMICS V20 Inverter
Operating Instructions, 11/2016, A5E34559884-006
Commissioning via the built-in BOP
5.6 Function commissioning
85