Parameter list
8.2 Parameter list
Parameter
Function
P0291[0...2]
Inverter protection
Bit 00 for enabling/disabling automatic pulse frequency reduction at output frequencies below 2 Hz. The
benefit is to reduce the noises at frequencies below 2 Hz.
Bit
00
01
02
Note:
See P0290
P0292
Inverter temperature
warning [°C]
Defines the temperature difference (in °C) between the overtemperature trip threshold (F4) and the warn-
ing threshold (A504) of the inverter. The trip threshold is stored internally by the inverter and cannot be
changed by the user.
P0294
Inverter I
Defines the [%] value at which warning A505 (inverter I
Inverter I
The I
t calculation value is deemed = 100 % when this maximum tolerable period is reached.
2
Dependency:
The output current of the inverter has been reduced.
The value of I
Note:
P0294 = 100 % corresponds to stationary nominal load.
P0295
Inverter fan off delay
time [s]
Defines inverter fan switch off delay time in seconds after inverter has stopped.
Note:
Setting to 0, inverter fan will switch off when the inverter stops, that means no delay.
P0301[0...2]
Easy motor data, rated
motor power [kW]
Rated motor power from the rating plate. No other data is necessary. If this parameter is used, the rest of
the motor data are then estimated by the firmware.
Dependency:
Changeable only when P0010 = 1 (quick commissioning).
Caution:
This functionality is only valid with 50 Hz supply, star configuration on 4-pole motors. You must set this
parameter to zero if you desire to set the other motor data.
200
Range
0 - 7
Signal name
Pulse frequency reduced below 2 Hz
Reserved
Phase loss detection enable
0 - 25
t warning [%]
10.0 - 100.0
2
t calculation is used to determine a maximum tolerable period for inverter overload.
2
t does not exceed 100 %.
2
0 - 3600
0 - 2000
Factory
Can be
Scaling
default
changed
1
T
-
1 signal
Yes
Yes
Yes
5
U, T
-
95.0
U, T
-
t) is generated.
2
0
U, T
-
0
C(1)
-
Operating Instructions, 11/2016, A5E34559884-006
Data
Data
Acc.
set
type
Level
DDS
U16
4
0 signal
No
No
No
-
U16
3
-
Float
3
-
U16
3
DDS
Float
1
SINAMICS V20 Inverter