Commissioning via the built-in BOP
5.6 Function commissioning
OFF2
The inverter pulses are immediately cancelled by the OFF2 command. Thus the motor
coasts down and it is not possible to stop in a controlled way.
Note
• The OFF2 command can have one or several sources. The command sources are
defined using BICO parameters P0844 (BI: 1. OFF2) and P0845 (BI: 2. OFF2).
• As a result of the pre-assignment (default setting), the OFF2 command is set to the BOP.
This source is still available even if another command source is defined (e.g. terminal as
command source → P0700 = 2 and OFF2 is selected using digital input 2 → P0702 = 3).
• OFF2 is active low.
• When various OFF commands are selected simultaneously, the following priority applies:
OFF2 (highest priority) – OFF3 – OFF1.
84
SINAMICS V20 Inverter
Operating Instructions, 11/2016, A5E34559884-006