Commissioning

5.7 Restoring to defaults

Setting parameter
Parameter
P0205
Function diagram
5.7
Restoring to defaults

Restoring to factory defaults

Parameter
Function
P0003
User access level
P0010
Commissioning parameter
P0970
Factory reset

Restoring to user defaults

Parameter
Function
P0003
User access level
P0010
Commissioning parameter
P0970
Factory reset
After setting the parameter P0970, the inverter displays "8 8 8 8 8" and then the screen
shows "P0970". P0970 and P0010 are automatically reset to their original value 0.
132
Function
Select inverter applications
Setting
= 1 (standard user access level)
= 30 (factory setting)
= 21: parameter reset to factory defaults deleting user defaults if
stored
Setting
= 1 (standard user access level)
= 30 (factory setting)
= 1: parameter reset to user defaults if stored, else factory de-
faults
Setting
This parameter selects the inverter appli-
cations on high overload and low over-
load:
=0: high overload
=1: low overload
SINAMICS V20 Inverter