Parameter
Function
P2375[0...2]
Motor destaging delay [s] 0 - 650
Time that PID error P2273 must exceed motor staging hysteresis P2373 before destaging occurs.
P2376[0...2]
Motor staging delay
override [%]
P2376 as a percentage of PID setpoint. When the PID error P2273 exceeds this value, a motor is staged /
destaged irrespective of the delay timers.
Note:
The value of this parameter must always be larger than staging hysteresis P2373.
P2377[0...2]
Motor staging lockout
timer [s]
Time for which delay override is prevented after a motor has been staged or destaged.
This prevents a second staging event immediately after a first, being caused by the transient conditions after
the first staging event.
P2378[0...2]
CO: Motor staging fre-
quency f_st [%]
The frequency as a percentage of maximum frequency. During a (de) staging event, as the inverter ramps
from maximum to minimum frequency (or vice versa) this is the frequency at which the digital output is
switched.
This is illustrated by the following diagrams.
SINAMICS V20 Inverter
Operating Instructions, 11/2016, A5E34559884-006
Range
Factory
default
30
0.0 - 200.0
25.0
0 - 650
30
0.0 - 120.0
50.0
Can be
Scaling
changed
U, T
-
U, T
PERCENT
U, T
-
U, T
PERCENT
Parameter list
8.2 Parameter list
Data
Data
Acc.
set
type
Level
DDS
U16
3
DDS
Float
3
DDS
U16
3
DDS
Float
3
295