Siemens SINAMICS V20 Operating Instructions Manual page 294

Hide thumbs Also See for SINAMICS V20:
Table of Contents

Advertisement

Parameter list
8.2 Parameter list
Parameter
Function
By default the motor states are controlled from digital outputs.
In the text below, the following terminology will be used:
MV - Variable speed (Inverter controlled motor)
M1 - Motor switched with digital output 1
M2 - Motor switched with digital output 2
Staging: The process of starting one of the fixed speed motors.
De-staging: The process of stopping one of the fixed speed motors.
When the inverter is running at maximum frequency, and the PID feedback indicates that a higher speed is
required, the inverter switches on (stages) one of the digital output controlled motors M1 and M2.
At the same time, to keep the controlled variable as constant as possible, the inverter must ramp down to
minimum frequency.
Therefore, during the staging process, PID control must be suspended (see P2378 and diagram below)
When the inverter is running at minimum frequency, and the PID feedback indicates that a lower speed is
required, the inverter switches off (de-stages) one of the digital output controlled motors M1 and M2.
In this case, the inverter must ramp from minimum frequency to maximum frequency outside of PID control
(see P2378 and diagram below).
P2372[0...2]
Motor staging cycling
Enables motor cycling for the motor staging feature.
When enabled, the motor selected for staging / destaging is based on the hours run counter P2380. When
staging, the motor with the least hours is switched on. When destaging, the motor with most hours is
switched off.
If staged motors are different sizes the choice of motor is first based on required motor size, and then if there
is still a choice, on hours run.
0
1
P2373[0...2]
Motor staging hysteresis
[%]
P2373 as a percentage of PID setpoint that PID error P2273 must be exceeded before staging delay starts.
Note:
The value of this parameter must always be smaller than delay override lockout timer P2377.
P2374[0...2]
Motor staging delay [s]
Time that PID error P2273 must exceed motor staging hysteresis P2373 before staging occurs.
294
Range
Factory
default
0 - 1
0
Disabled
Enabled
0.0 - 200.0
20.0
0 - 650
30
Can be
Scaling
changed
T
-
U, T
PERCENT
U, T
-
Operating Instructions, 11/2016, A5E34559884-006
Data
Data
Acc.
set
type
Level
DDS
U16
3
DDS
Float
3
DDS
U16
3
SINAMICS V20 Inverter