Parameter list
8.2 Parameter list
Parameter
Function
Note:
See P0947 (last fault code)
Automatically reset to 0.
P3984
Client telegram off time
[ms]
Defines time after which a fault will be generated (F73) if no telegram is received from the client.
Dependency: Setting 0 = watchdog disabled
r3986[0...1]
Number of parameters
Number of parameters on the inverter.
Index:
[0]
[1]
r4000 - r4064 Reserved
P7844
Acceptance test, con-
firmation
After an automatic download from the SD card at startup, this parameter will be automatically set to 1. Also
a fault F395 will be set.
With setting to P7844 = 0 you quit F395 and confirm the parameter settings. Setting this parameter to 2 is
only possible if an automatic download has been performed at startup. In this case the download will be
undone and the previously stored parameters will be enabled.
0
1
2
Note:
If no automatic download from the SD card has been performed during startup the setting 2 is not possible.
If the clone file contains user defaults and the cloning at startup is rejected with P7844 = 2, parameters are
set to the user defaults in the clone file instead of the previously saved values.
P8458
Clone control
This parameter specifies whether a cloning at startup will be performed. The File clone00.bin will be used. If
no SD card is inserted there will be a normal startup.
0
1
2
3
4
Note:
Default value is 2. After first cloning the parameter is set to 0. If an SD card is inserted without a valid file
the inverter will set a fault F61 / F63 / F64 which can only be cleared by a power-cycle. The fault is signaled
by a flashing RUN LED (Commissioning). The SF LED is not activated. P8458 will not be changed by per-
forming a factory reset.
P8553
Menu type
Selects whether to have menus with no text or menus with some text on the BOP.
0
1
318
Range
Factory
default
100 - 10000
1000
-
-
Read only
Read & write
0 - 2
0
Acceptance test / confirmation OK
Acceptance test / confirmation is pending
Undo clone
0 - 4
2
No startup cloning
Clone at startup once
Clone at startup always
Clone at startup once, except the motor data
Clone at startup always, except the motor data
0 - 1
0
Menus with no text
Menus with some text
Can be
Scaling
changed
T
-
-
-
T
-
C, T
-
U, T
-
Operating Instructions, 11/2016, A5E34559884-006
Data
Data
Acc.
set
type
Level
-
U16
3
-
U16
4
-
U16
3
-
U16
3
-
U16
1
SINAMICS V20 Inverter