Setting The Imax Controller - Siemens SINAMICS V20 Operating Instructions Manual

Hide thumbs Also See for SINAMICS V20:
Table of Contents

Advertisement

Commissioning via the built-in BOP
5.6 Function commissioning
5.6.2.7

Setting the Imax controller

Functionality
If ramp-up time is too short, the inverter may display the alarm A501 which means the output
current is too high. The Imax controller reduces inverter current if the output current exceeds
the maximum output current limit (r0067). This is achieved by reducing the inverter's output
frequency or output voltage.
104
SINAMICS V20 Inverter
Operating Instructions, 11/2016, A5E34559884-006