Siemens SINAMICS V20 Operating Instructions Manual page 196

Hide thumbs Also See for SINAMICS V20:
Table of Contents

Advertisement

Parameter list
8.2 Parameter list
Parameter
Function
P0205
Inverter application
Selects inverter application.
The inverter and motor requirements are determined by the speed range and torque requirements of the
load. The relationship between speed and torque for different loads (high overloads or low overloads) is
shown in the following figure:
High overload (HO):
HO mode is used if the application needs a high overload on the whole frequency range. Many loads
can be considered to be high overloads. Typical high overloads are conveyors, compressors and posi-
tive displacement pumps.
Low overload (LO):
LO mode is used if the application has a parabolic frequency/torque characteristic like many fans and
pumps. Low overload offers the following possibilities with the same inverter:
Higher rated inverter current r0207
Higher rated inverter power r0206
Higher threshold for I2t protection
If P0205 is modified in quick commissioning it immediately calculates various motor parameters:
P0305 Rated motor current
P0307 Rated motor power
P0640 Motor overload factor
It is recommended to modify P0205 first. Afterwards motor parameter may be adapted.
Motor parameter will be overridden by changing this sequence.
Values:
0
1
Notice:
Use setting 1 (low overload) only for low-overload applications (for example, pumps and fans).
If it is used for high-overload applications, I2t warning will be produced too late, causing overheating in the
motor.
196
Range
Factory
default
0 - 1
0
High overload
Low overload
Can be
Scaling
changed
C1
-
Operating Instructions, 11/2016, A5E34559884-006
Data
Data
Acc.
set
type
Level
-
U16
3
SINAMICS V20 Inverter

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents