Faults and alarms
9.1 Faults
Viewing inverter status at fault
Fault code list
Fault
F1
Overcurrent
F2
Overvoltage
320
Cause
Motor power (P0307) does not cor-
•
respond to the inverter power
(r0206).
Motor lead short circuit
•
Earth faults
•
r0949 = 0: Hardware reported
r0949 = 1: Software reported
r0949 = 22: Hardware reported
Main supply voltage too high
•
Motor is in regenerative mode
•
r0949 = 0: Hardware reported
r0949 = 1 or 2: Software reported
Remedy
Check the following:
Motor power (P0307) must correspond to in-
•
verter power (r0206).
Cable length limits must not be exceeded.
•
Motor cable and motor must have no short-
•
circuits or earth faults.
Motor parameters must match the motor in use.
•
Value of stator resistance (P0350) must be
•
correct.
Motor must not be obstructed or overloaded.
•
Increase ramp-up time (P1120)
•
Reduce starting boost level (P1312)
•
Check the following:
Supply voltage (P0210) must lie within limits
•
indicated on rating plate.
Ramp-down time (P1121) must match inertia of
•
load.
Required braking power must lie within specified
•
limits.
Vdc controller must be enabled (P1240) and
•
parameterized properly.
Note:
Regenerative mode can be caused by fast ramp
downs or if the motor is driven by an active load.
Higher inertia requires longer ramp times; other-
wise, apply braking resistor.
Operating Instructions, 11/2016, A5E34559884-006
SINAMICS V20 Inverter