Setting Application Macros; Setting Common Parameters; Restoring To Defaults - Siemens Sinamics V20 Operating Instructions Manual

Hide thumbs Also See for Sinamics V20:
Table of Contents

Advertisement

3.2.3

Setting application macros

Functionality
This menu defines certain common applications. Each application macro provides a set of parameter settings for a specific
application. After you select an application macro, the corresponding settings are applied to the inverter to simplify the
commissioning process.
Application macro specific parameters
Parameter Description
P1080[0]
Minimum frequency
P1300[0]
Control mode
P1110[0]
BI: Inhibit negative
frequency setpoint
P1200[0]
Flying start
P1210[0]
Automatic restart
P1120[0]
Ramp-up time
P1121[0]
Ramp-down time
P1312[0]
Starting boost
P1311[0]
Acceleration boost
P1310[0]
Continuous boost
3.2.4

Setting common parameters

Parameter
Description
P1080[0]
Minimum motor frequency
P1082[0]
Maximum motor frequency
P1120[0]
Ramp-up time
P1121[0]
Ramp-down time
P1058[0]
JOG frequency
P1060[0]
JOG ramp-up time
3.3

Restoring to defaults

Parameter
Function
P0003
User access level
P0010
Commissioning parameter
P0970
Factory reset
After the setting for P0970, the inverter displays "8 8 8 8 8" and then the screen shows "P0970". P0970 and P0010 are
automatically reset to their original value 0.
16
Factory
Default for application macro
default
AP010 AP020 AP021 AP030
0
15
20
0
7
7
0
1
-
0
-
2
1
2
2
10
10
10
10
10
20
0
-
-
0
-
-
50
-
Setting
= 1 (standard user access level)
= 30 (factory setting)
= 1: parameter reset to user defaults if stored, else factory
defaults (restoring to user defaults)
= 21: parameter reset to factory defaults deleting user defaults if
stored (restoring to factory defaults)
Remarks
-
-
Inverter running at a lower speed inhibited
0
1
=7: Quadratic V/f
=0: Linear V/f
=1: V/f with FCC
-
-
Reverse rotation inhibited
-
-
Search for the speed of the running motor
with a heavy inertia load so that the motor
runs up to the setpoint
-
-
Fault acknowledgement at power-on
10
5
Ramp-up time from zero to maximum
frequency
10
5
Ramp-down time from maximum frequency
to zero
30
30
Boost only effective when accelerating for
the first time (standstill)
0
-
Boost only effective when accelerating or
braking
50
-
Additional boost over the complete
frequency range
Parameter
Description
P1001[0]
Fixed frequency setpoint 1
P1002[0]
Fixed frequency setpoint 2
P1003[0]
Fixed frequency setpoint 3
P2201[0]
Fixed PID frequency setpoint 1
P2202[0]
Fixed PID frequency setpoint 2
P2203[0]
Fixed PID frequency setpoint 3
Getting Started