Siemens SINAMICS V20 Operating Instructions Manual page 74

Hide thumbs Also See for SINAMICS V20:
Table of Contents

Advertisement

Commissioning via the built-in BOP
5.5 Quick commissioning
Functionality
This menu defines certain common applications. Each application macro provides a set of
parameter settings for a specific application. After you select an application macro, the
corresponding settings are applied to the inverter to simplify the commissioning process.
The default application macro is "AP000" for application macro 0. If none of the application
macros fits your application, select the one that is the closest to your application and make
further parameter changes as desired.
Application macro
Description
AP000
Factory default setting. Makes no parameter
changes.
AP010
Simple pump applications
AP020
Simple fan applications
AP021
Compressor applications
AP030
Conveyor applications
Setting application macros
Application macro AP010 - Simple pump applications
Parameter Description
P1080[0]
Minimum frequency
P1300[0]
Control mode
P1110[0]
BI: Inhibit negative frequen-
cy setpoint
P1210[0]
Automatic restart
P1120[0]
Ramp-up time
P1121[0]
Ramp-down time
74
Factory default
Default for
AP010
0
15
0
7
0
1
1
2
10
10
10
10
Display example
The minus sign indicates that this macro is the cur-
rently selected macro.
Remarks
Inverter running at a lower speed inhibited
Quadratic V/f
Reverse pump rotation inhibited
Restart after mains blackout
Ramp-up time from zero to maximum fre-
quency
Ramp-down time from maximum frequency
to zero
Operating Instructions, 11/2016, A5E34559884-006
SINAMICS V20 Inverter