Communicating with the PLC
The SINAMICS V20 supports communication with Siemens PLCs over USS on RS485. You
can parameterize whether the RS485 interface shall apply USS or MODBUS RTU protocol.
USS is the default bus setting. A screened twisted pair cable is recommended for the RS485
communication.
Make sure that you terminate the bus correctly by fitting a 120 R bus termination resistor
between the bus terminals (P+, N-) of the device at one end of the bus and a termination
network between the bus terminals of the device at the other end of the bus. The termination
network should be a 1.5 k resistor from 10 V to P+, 120 R from P+ to N- and 470 R from N-
to 0 V. A suitable termination network is available from your Siemens dealer.