IPIDController function
block operation
Input Auto
When Input Auto is TRUE, the IPIDController runs in normal auto mode.
When Input Auto is FALSE, it causes reset R to track (F-GE) forcing the
IPIDController Output to track the Feedback within the IPIDController limits
at which time the controller switches back to auto without incrementing the
Output.
Input Initialize
For Input Initialize, changing from FALSE to TRUE or TRUE to FALSE when
AutoTune is FALSE causes the IPIDController to eliminate any proportional
gain action during that cycle (for example, Initialize). You can use this process to
prevent bumping the Output when changes are made to the SetPoint using a
switch function block.
Rockwell Automation Publication 2080-RM001D-EN-E - February 2015
Proportional Integral Derivative (PID) instruction
Chapter 20