Chapter 18
Process control instructions
Parameter
EN
On
Freq
DutyCycle
ChType
ChSlot
ChNum
Sts
ENO
540
PWM arguments
Parameter type
Data
Description
type
Input
BOOL
Function block enable. This level is FB triggered.
When EN = TRUE, Sts is updated. PWM is made active or inactive depending on the On input
parameter and valid configuration.
When EN = FALSE, Sts is only updated. PWM state (active or inactive) is not affected..
Input
BOOL
Turns the PWM output On/Active or Off/Inactive.
TRUE = PWM output is made active or continues to be active with latest valid configuration.
Output LED is ON when PWM is active, even if duty cycle is set to 0%.
FALSE = PWM output is made inactive but only if configuration is also valid.
Input
UDINT
Frequency in Hz
• 1 – 100000
Input
UINT
Duty Cycle
• 0 – 1000 (0% - 100%)
Input
USINT
Channel Type
• 0 – Embedded
• 1 – Plugin
• 2 – Expansion
Input
UINT
Channel Slot
• 0 – Embedded
Input
UINT
Channel Number
• 0 – PWM CH0
Output
UINT
Function block execution status.
00 - Function block not enabled (no operation.)
01 - PWM configuration successful.
02 - Invalid duty cycle.
03 - Invalid Frequency.
04 - Invalid Channel Type.
05 - Invalid Channel Slot.
06 - Invalid Channel Number.
07 - Invalid Catalog. PWM feature is not supported in the catalog being used.
Output
BOOL
Enable out.
Applies only to LD programs.